Control/Sequence Group; Inhibit Group; Channel; Operating Sequence Configuration - Ametek DMS-3K Installation & Operation Manual

Distributed monitoring system
Table of Contents

Advertisement

Control/Sequence Group:

This is used to assign the control input to any of 8 groups. The groups correspond to specific
alarm inputs as configured in the Alarm Inputs page. For example: If you wanted a test
pushbutton to only operate specific alarm inputs, you would designate that group number for
the test pushbutton and assign it to all inputs in the Alarm Inputs configuration page.
Control Group 1 is a global 'system-wide' group that controls all inputs regardless of which
control group is assigned.
For example: If Input channel #23 is configured for Control Group 4 (reference the Alarm Inputs
Configuration screen), any pushbutton assigned to Control Group 4 will control that input
channel #23. In addition, any pushbutton assigned to Control Group 1 will also control the same
input channel #23.

Inhibit Group:

Similar to above but with the Inhibit Switch inputs.

Channel:

This will display an abbreviation of the control switch and group number configured.

Operating Sequence Configuration:

Up to 12 operating sequences can be configured for each Logic Card Rack. The available
operating sequences are:
• ISA-A
• ISA-A-4
• ISA-A-4-5-6 Automatic reset, non-locking, no flash, no audible, NO PB
• ISA-M
• ISA-F1A-1
• ISA-F2A-1
• ISA-F2M-1
• ISA-F3A
• ISA-F3M
• ISA-FFAM2 First Out, manual reset
• ISA-R
• ISA-R-12
Refer to Appendix H for a list of all operating Sequences and their operation.

Control Interlock:

This requires that the Silence, Acknowledge and Reset pushbuttons are pressed in this exact
order. Anything else will be ignored.
For example; if the Acknowledge pushbutton is pressed before the Silence, it will not have any
effect. (Note: If the Reset function is not required for the alarm sequence selected, it will be
ignored.)
62
Automatic reset with lock-in of alarms
Automatic reset with no lock-in of alarms
Manual Reset with lock-in of alarms
First Out Flash, Subsequent alarm steady, auto reset
First Out, Fast Flash, auto reset
First Out, no subsequent alarm flash, manual reset
First Out, triple flash, first out reset
First out, triple flash, first out manual reset
Ringback, separate flash for return to normal
Automatic Momentary Ringback, dual flash, manual reset