Alarm Outputs Configuration
Notes:
Input #1-8 are assigned to Lamp outputs #1-8
Input #9-16 are assigned to Lamp outputs #9-16
I/R Card installed in slot #10 corresponds to Outputs 129,130,131 as shown
Output 129 configured as a Horn with all inputs assigned to it. Auto-silence configured
for 10 seconds. (It will operate when any input 1-16 goes into alarm and will be
silenced by either the Acknowledge pushbutton or automatically in 10 seconds)
Output 130 configured as a 'Group Relay - Alarm Output', follows field contact,
assigned to inputs 1-8. (It will operate when any input 1-8 goes into alarm and stay
activated until all alarms return to normal)
Output 131 configured as a 'Group Relay - Alarm Output', follows field contact,
assigned to inputs 9-16. (It will operate when any input 9-16 goes into alarm and stay
activated until all alarms return to normal)
72
(8 I/O card in slot #1)
(8 I/O card in slot #2)