Ametek DMS-3K Installation & Operation Manual page 132

Distributed monitoring system
Table of Contents

Advertisement

Reg-94 (Reg-95) Module Specifications
SYSTEM SUPPLY
Nominal Supply Voltage:
Minimum Supply Voltage:
Maximum Supply Voltage:
The System supply voltage must be regulated and within the limits of 44-63V DC and is used for Lamp Voltage,
Control Switches, Audible Supply and for Alarm Contact wetting when using the REG-94.
The REG-95 should be used if the inputs are to be supplied independently of the system supply. This Isolated
Input supply must match the voltage rating of the Input or Output modules installed in the Logic Crate
OUTPUT 1 (Internal)
Logic supply:
Relay
Audible (or Auxiliary) relay
COMPATIBITY TABLE
The DMS-3K module range is fully backwards compatible with previous versions of this product, namely:
MPAS90
(Highland Electronics Limited)
RTU3000
Rochester Instrument systems Limited
DMS3000
AMETEK Power Instruments Limited
The REGULATOR modules are backward compatible per the following table
DMS-3K MODULE
Module Ref
Part No*
REG-94B
1087-415
REG-95B
1087-419
(*Assembly Part Numbers listed include Front Panel and Wiring Connectors)
120
48V DC
44V DC
63V DC
5V DC ± 0.25v @ 5.0 Amp Maximum
Short Circuit Protected
The 5V Supply is not available as an output
DO NOT attempt to use this supply for external use.
60V Coil
Rating 2 Amp @240V a.c. Max
Form A (Normally Open) Contact
COMPATIBLE MODULES
Module Ref
Part No
REG-94A
8025-235
REG-95A
8025-242
Comment
Two part Edge Connector
Two part Edge Connector