-Modbus Communication Outputs to Annunciator
In this configuration, the DMS-3K System uses either Serial (RS-232/485) or Ethernet
communications with Modbus TCP/IP Protocol to transmit alarm inputs to a remote
Annunciator. The Modbus configuration allows you to map individual or groups of alarm inputs
to the Modbus Outputs up to the maximum 128 Modbus outputs. The communication outputs
are provided on the system CPU and use either a DB9 or RJ45 connector.
The following Annunciators are compatible with the communication lamp outputs:
• AN-3100D / Series 90A
• AN-6100C / Series 100
14
This display can be configured in cell configurations up to 13 rows high by 13
columns wide and each cell has 4 window sizes available: Quad 1.5H x 1.5W",
Triple 1.0H x 3.0W", Dual 1.5H x 3.0W", Single 3.0H x 3.0W". There is a
maximum of 50 cells in any Annunciator. Customer connections can be made
using a DB9 or RJ45. The display comes with LED lamps as standard.
This display can be configured in cell configurations up to 5 rows high by 5
columns wide (max 25 cells) and each cell has 4 window sizes available: Small
0.98H x 1.14W", Medium 0.98W x 2.40H", Large 2.13H x 2.40W", Extra large
2.13H x 4.96W". Customer connections can be made using a DB9 or RJ45. The
display comes with LED lamps as standard.