5.5.5.2 Commissioning a Temperature Sensor (Connected to the NTC port
on the rack environment unit)
If a temperature sensor is installed, perform the following steps to configure it.
Procedure
Step 1 The temperature sensor supports self-discovery and does not need to set parameters.
Step 2 Check the monitoring functions of temperature sensor.
Table 5-30 Commissioning the sensor
Check Method
Path: Monitoring > Cabinet >
IT Cabinet n > Cabinet
Collector n
----End

5.5.6 Commissioning a T/H Sensor

5.5.6.1 Commissioning a T/H Sensor (BOM number:33010346)

If a T/H sensor is installed, perform the following steps to configure it.
Procedure
Step 1 Set the T/H sensor device address.
1.
Step 2 Add a T/H sensor.
1.
2.
Table 5-31 Adding a T/H sensor
Path
Choose System
Settings >
Device
Management
and click Add
Device. The
parameters for
adding devices
Issue 07 (2020-03-16)
Go to the LCD screen of the T/H sensor. Press SET to go to the ADD screen, and set the
device address to 1 by pressing + or –.
Log in to the ECC800 WebUI as an administrator.
Add a T/H sensor.
Parameter
Name
Device attribute
Device type
Connect To
Communications
port
Copyright © Huawei Technologies Co., Ltd.
Normal Connection Status
You can view the current cabinet temperature.
Setting
Select Sensor from the drop-down list box.
Select T/H sensor from the drop-down list box.
Select ECC800 from the drop-down list box.
Select COM3 from the drop-down list box.
NOTE
The setting example indicates that the T/H sensor is
5 Power-On Commissioning
123