7.2.2 Setting SNMP Management Parameters

Prerequisites
Before setting SNMP parameters, obtain the information listed as follows from the NMS.
Table 7-3 Information obtained from the NMS
Item
SNMP version
SNMP port number
Read community
name
Write community
name
User name
MD5/SHA password
DES/AES password
Trap target address
Trap port
Context
Procedure
Step 1 Apply to the equipment room network administrator for a fixed IP address.
Step 2 Set the IP address, subnet mask, and default gateway on the ECC800 WebUI.
Table 7-4 IP parameters
Path
System
Settings >
Monitor
Module
IP >
Issue 07 (2020-03-16)
Default
Value
SNMPv3
161
N/A
N/A
N/A
N/A
N/A
N/A
162
SNMPv3 parameters should be set before connecting the ECC800 to the NMS. These
parameters are required for setting up the ECC800 on the NMS.
SNMPv1 and SNMPv2c are insecure. Therefore, SNMPv3 is recommended. This
section uses SNMPv3 as an example.
Item
IP
Subnet mask
Copyright © Huawei Technologies Co., Ltd.
Description
SNMP version and port number used by the ECC800
and NMS. The SNMP versions include SNMPv1,
SNMPv2c, and SNMPv3.
If you use SNMPv1 or SNMPv2c, enter the read and
write community names that comply with the NMS.
Otherwise, the ECC800 will not connect to the
NMS. The read community name must be different
from the write community name.
To enhance the security, you need a user name and
password for authentication if you use SNMPv3.
After the authentication succeeds, the ECC800 can
communicate with the NMS.
IP address of the NMS server.
Port defined by the user.
Default
Setting
Value
192.168.1.10
Set this parameter based on the IP address
assigned by the network administrator.
255.255.255.
Set this parameter based on the subnet mask
0
assigned by the network administrator.