ECC800 Data Center Controller
User Manual

3.2.18.2 BIM

The BIM is a battery monitoring module that monitors the voltages, internal resistances, and
pole temperatures of batteries and supports 12 V power.
Features
BIM Appearance
Figure 3-44 BIM
Indicators
Table 3-69 Indicator description
Indicator
Running
Alarm
Issue 07 (2020-03-16)
Monitors the voltages, internal resistances, and pole temperatures of 12 V batteries.
Supports the hibernation function. (When it detects that the battery voltage is low, it will
enter the low-power mode.)
Communicates with the CIM wirelessly.
Color
Silk
Screen
Green
RUN
Red
ALM
Copyright © Huawei Technologies Co., Ltd.
Status
Description
Off
Power consumption is low or the
BIM is not powered on.
Blinking at
The networking has started but not
completed.
super short
intervals
Blinking at
The networking succeeds.
long intervals
Off
The BIM is not faulty.
Steady on
The BIM is faulty.
Communication with the CIM
times out.
No network is connected. (The
BIM is waiting to connect to a