ECC800 Data Center Controller
User Manual
Path
WAN_1
Step 3 Set SNMP parameters.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10. After setting the parameters, click Confirm.
11. Click Export in the Mib File pane, export the Mib file, and send to the development
----End
Issue 07 (2020-03-16)
Item
Default
gateway
Choose System Settings > SNMP Settings.
Set SNMP version to SNMPv3 and set SNMP port number to the required port
number or retain its default value 161.
Click Submit under SNMP.
Click Add in SNMPv3.
Set User name, set Authentication protocol to SHA or MD5, set Privacy protocol to
AES or DES, and specify MD5/SHA password, Confirm MD5/SHA password,
DES/AES password, and Confirm DES/AES password.
Set User name, MD5/SHA password, and DES/AES password to any character strings that meet
the system requirements. Note that MD5/SHA password and DES/AES password must be set to
different values. Record the settings.
MD5 and DES are insecure protocols. Therefore, you are advised to set Authentication protocol to
SHA or set Privacy protocol to AES.
Set Password validity period and Advance expiration notification (days).
After setting the parameters, click Confirm.
Click Add under SNMP Trap.
Set Trap target address and Trap port, set SNMP version to SNMPv3, and specify
SNMPv3 user name. Set Trap target address to the IP address of the NMS server and
set Trap port to the port defined by the user.
engineers of the NMS.
Copyright © Huawei Technologies Co., Ltd.
Default
Setting
Value
192.168.1.1
Set this parameter based on the default
gateway address assigned by the network
administrator.
7 Remote Management