Huawei ECC800 User Manual page 78

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
Pin
Definition
3
NO
4
COM
HALL Current Monitoring Port
Figure 3-42 HALL Current monitoring port pins
Table 3-62 HALL Current monitoring port pin definitions
Pin
1
2
3
4
Issue 07 (2020-03-16)
Signal
Description
Dry contract
output signal
If the battery string is configured with the neutral wire, measure the currents of the positive and
negative battery string cables. If the battery string is not configured with the neutral wire, measure
the current of either the positive or negative battery string cable. The following uses the scenario
where the battery string is configured with the neutral wire as an example.
When a CIM manages multiple battery strings, first connect the Hall effect sensors on the positive
and negative cables of battery string 1 respectively to the corresponding ports on the CIM. Then
connect the Hall effect sensors on battery string 2 to the CIM in the same way, and so on.
If the positive or negative battery string cable is too thick to be routed through the Hall effect sensor,
or the measurement range of the Hall effect sensor is not enough, use multiple Hall effect sensors to
monitor the current of one battery string. The CIM supports the sum of the monitoring results of
multiple Hall effect sensors, which is set through Multi-Hall cur. setting.
Copyright © Huawei Technologies Co., Ltd.
Status
Description
closed.
Open: The
dry contact
output is
open.
Closed: The
dry contact
output is
closed.
Definition
+12 V
–12 V
AI
GND
3 Device Description
Initial Status
Remarks
Open
Description
Detect the charge and
discharge currents of four
battery strings or eight
battery routes.
69