Huawei ECC800 User Manual page 116

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
1.
2.
Step 2 Add a PMAC615.
1.
2.
Table 5-14 Adding a PMAC615
Path
Choose System
Settings > Device
Management and
click Add Device.
The parameters for
adding devices are
displayed.
3.
Issue 07 (2020-03-16)
After the PMAC615 is started, press
screen is displayed. Press
communications address setting screen.
Press
and a blinking cursor is displayed. Press
address based on site requirements. Then press
Figure 5-9 PMAC615 communications address
Log in to the ECC800 WebUI as an administrator.
Add a PMAC615.
Parameter Name
Device attribute
Device Type
Connect To
Communications
Port
Device Address
Click Test Connect to check whether the PMAC615 connects to the ECC800 properly.
If the PMAC615 connects to the ECC800 properly, click Confirm. The connected
devices are displayed in the Number of connected devices list.
If the PMAC615 does not connect to the ECC800 properly, check whether the cable
between the PMAC615 and the ECC800 is connected properly, whether the
Copyright © Huawei Technologies Co., Ltd.
on the displayed screen and the configuration
until the ID prompt is displayed, indicating the
to confirm the address setting.
Setting
Select Electricity Meter from the drop-down
list box.
Select PMAC615 from the drop-down list
box.
Select ECC800 from the drop-down list box.
Select COM3 from the drop-down list box.
NOTE
The setting example indicates that the PMAC615 is
connected to the COM3 port on the ECC800. If the
PMAC615 is connected to another port, enter the
number of the connected port.
In this example, Device Address is set to 8.
During actual configuration, set the device
address for the PMAC615 based on the actual
situation.
5 Power-On Commissioning