How To Set And Add A Pdu8000 (Over Modbus Rtu) - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
Context
The method of connecting the PDU8000 to the ECC800 is the same as that for the integrated
PDU. Connecting the integrated PDU to the ECC800 by following the instructions in this
section.
Procedure
Step 1 Set the PDU8000 monitoring parameters.
1.
2.
3.
----End

5.3.11 How to Set and Add a PDU8000 (over Modbus RTU)?

Prerequisites
One end of the straight-through cable has been connected to the COM port on the PDU8000,
and the other end has been connected to the COM port on the ECC800 collector, rack
environment unit, or ETH converter.
Procedure
Step 1 Set the PDU8000 monitoring parameters.
1.
2.
3.
Issue 07 (2020-03-16)
Enter thePDU8000 home page, tap System Info.
Choose System Info > Settings, enter the user name admin and password 000001, and
press
.
Tap Communication to set IP address assign to Automatic(DHCP) on the displayed
communication settings screen and the PDU8000 is discovered by ECC800
automatically and is connected to the ECC800.
Enter the PDU8000 home page, tap System Info.
Choose System Info > Settings, enter the user name admin and password 000001, and
press
. In the password message dialog box displayed, click Confirm.
Tap Communication and check IP address assign to Manual. And set Serial port
baud rate to 9600, and Serial port address to 1 on the displayed communication
settings screen.
Copyright © Huawei Technologies Co., Ltd.
5 Power-On Commissioning
97

Advertisement

Table of Contents
loading

Table of Contents