Step 5 Calculate the PUE of the smart module. PUE = (Increment in the total active electricity
energy of the device input)/(Increment in the total power consumption of the branch IT load
output)
Step 6 You can also view the PUE in the dashboard or PUE Chart on the home page.
----End
Issue 07 (2020-03-16)
page, select Integrated PDU 1 and on the Select Indicators tab page, select 1QF4
electricity energy, 1QF5 electricity energy, and 1QF6 electricity energy, and click
Confirm.
Figure 6-8 IT cabinet power consumption configuration
Under Total Power Consumption Configuration and IT Cabinet Power
Consumption Configuration, click the edit icon on the right to modify the multiple for
calculating indicators, as shown in
Figure 6-9 Editing a multiple
The multiple ranges from 0.01 to 4.99, with two significant digits. The default value is 1.00.
The multiple is configured for slightly adjusting the calculated PUE, ensuring that the calculated
PUE is as close as possible to the actual PUE.
Performance data source: The ECC800 obtains total electricity energy of branches from the power
distribution devices.
Copyright © Huawei Technologies Co., Ltd.
Figure
6-9.
6 Feature Description
169