Setting Netcol5000-C030 Parameters (Over Modbus Tcp); How Do I Set And Add A Netcol5000-C030 (Over Modbus Rtu) - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual

5.3.5 Setting NetCol5000-C030 Parameters (over Modbus TCP)

Prerequisites
In this example, a straight-through cable is used to connect the NetCol5000-C030 to the POE
port on the smart ETH gateway.
Procedure
Step 1 Set NetCol5000-C030 monitoring parameters.
1.
2.
3.
Step 2 Set the running parameters and control parameters for the NetCol5000-C030 on the WebUI.
1.
2.
3.
4.
----End
5.3.6 How Do I Set and Add a NetCol5000-C030 (over Modbus
RTU)?
Prerequisites
In this example, a straight-through cable is used to connect the NetCol5000-C030 to the COM
port on the ECC800.
Procedure
Step 1 Set NetCol5000-C030 monitoring parameters.
Issue 07 (2020-03-16)
Enter the NetCol5000-C030 home page, click Settings, choose user name Admin and
enter password 000001. After login, the settings screen of the NetCol5000-C030 is
displayed.
Choose Settings > Comm Settings > IP Settings, set IP assigning mode to
Automatic(DHCP), and tap Submit.
Choose Settings > Comm Settings > Modbus Settings, and set Connection mode to
Server, Server encryption to Enable.
After setting parameters for the NetCol5000-C030, the ECC800 discovers the access from the air
conditioner automatically.
The earlier version has Protocol setting on the screen. The actual screen prevails.
Log in to the ECC800 WebUI as an administrator.
Choose Monitoring > Air Conditioner > NetCol5000-C0301.
0301 in NetCol5000-C0301 is variable and subject to change with the air conditioner model and
connection sequence. 030 indicates the 30 kW model, and 1 indicates the air conditioner connection
sequence. The displayed value prevails.
On the Running Parameters tab page, set air conditioner running parameters,
temperature and humidity parameters, and alarm parameters.
On the Controls tab page, set the air conditioner control parameters (such as on/off
control parameters).
Copyright © Huawei Technologies Co., Ltd.
5 Power-On Commissioning
92