Commissioning The Ac Actuator (Wireless Networking) - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
Context
Procedure
Step 1 Log in to the ECC800 WebUI as an administrator.
Step 2 Choose Monitoring > System > ECC800 > Running Parameters.
Step 3 On the Online Detection Timeout Interval tab page, set Online detection timeout interval
to 29. Click Submit.
Step 4 On the IP Device Number tab page, set IP device num to 5.
Step 5 Click Submit. The IP Device 1-5 tab page is displayed.
Step 6 On the IP Device 1-5 tab page, set Enable online detection IP device 1 to Enable.
Step 7 Click Submit.
Step 8 Specify IP device 1 address.
Step 9 Click Submit.
Step 10 (Optional) If you need to change the name of an IP device, perform the following steps:
1.
2.
3.
----End
5.4 Commissioning the AC Actuator (Wireless
Networking)
If an AC actuator with wireless networking is configured, perform the following steps to set
its parameters.
Issue 07 (2020-03-16)
IP devices, such as ATMs, are devices with IP attributes in an equipment room or site. By
adding a IP device, you connect the device to the ECC800 in the same network so that
the ECC800 monitors the device status. If the IP device is offline, the ECC800 will
report a disconnection alarm on its WebUI.
Following is a procedure example about how to add five IP devices with the online
detection timeout interval being 29 seconds.
Online detection timeout interval is 30 by default, which means that the ECC800 determines that the
communication with the device is interrupted if the device has no response within 30 seconds.
Set IP device 1 address to the IP address of IP device 1. For example, set IP device 1 address to
XXX.XXX.X.XXX.
Add other IP devices in the same way.
Choose System Settings > Signal Name Modify. The Batch Signal Configuration
page is displayed.
Set Device Type to ECC800, set Device Name to ECC800, and click OK.
On the query result tab page, set the new signal name of IP device 1 to XXX and click
Submit.
Copyright © Huawei Technologies Co., Ltd.