How Do I Set And Add A Sunrise Scu-20K - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
2.
Table 5-4 Adding a UPS5000-E
Path
Choose System
Settings >
Device
Management
and click Add
Device. The
parameters for
adding devices
are displayed.
3.
4.
----End

5.3.4 How Do I Set and Add a SUNRISE SCU-20K?

Prerequisites
In this example, a straight-through cable is used to connect the SUNRISE-SCU-20K to the
COM port on the ETH converter.
When connecting devices, you are advised to add devices one by one and ensure that the view
is consistent with the real object. If all devices have been added and powered on, only the
BLINK function of the ETH converter can be used to identify the mapping between the
SUNRISE-SCU-20K and ETH converter.
Procedure
Step 1 Set the SUNRISE-SCU-20K monitoring parameters.
1.
2.
Issue 07 (2020-03-16)
Add a UPS5000-E.
Parameter
Name
Device attribute
Device Type
Connect To
Communications
Port
Device Address
Click Test Connect to check whether the UPS5000-E connects to the ECC800 properly.
If the UPS5000-E connects to the ECC800 properly, click Confirm. The connected
devices are displayed in the Number of connected devices list.
If the UPS5000-E does not connect to the ECC800 properly, check whether the
cable between the UPS5000-E and the ECC800 is connected properly, whether the
UPS5000-E and ECC800 are running properly, and whether the input parameters
are consistent with the UPS5000-E parameters.
Choose Monitoring > System > ETH Converter Group > ETH Converter n >
Running Parameters and set Device name to ETH Converter n_Device name.
After SUNRISE-SCU-20K startup, tap Settings on the home screen and enter the
password 111111 to enter the parameter settings screen.
Choose Settings > Comm Settings, and set Monitoring baud rate to 9600, and set
Monitoring address based on site requirements.
Copyright © Huawei Technologies Co., Ltd.
Setting
Select UPS from the drop-down list box.
Select UPS5000 from the drop-down list box.
Select ETH Converter n from the drop-down list
box.
Select COM1/COM2 from the drop-down list box.
In this example, Device Address is set to 1. During
actual configuration, set the device address for the
UPS5000-E based on the actual situation.
5 Power-On Commissioning
90