How To Set And Add The Temperature Sensor (Connected To The Ntc Port On The Rack Environment Unit) - Huawei ECC800 User Manual

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
2.
3.
4.
5.
6.
7.
Step 2 Check the monitoring functions of the temperature sensor.
Table 8-29 Commissioning the sensor
Check Method
View the operating information
about the temperature sensor on
the WebUI.
----End
8.1.8.34 How to Set and Add the Temperature Sensor (Connected to the
NTC Port on the Rack Environment Unit)?
If a temperature sensor is installed, perform the following steps to configure it.
Prerequisites
One end of the straight-through cable has been connected to the RJ45 port on the temperature
sensor, and the other end has been connected to the NTC port on the rack environment unit.
Procedure
Step 1 The temperature sensor supports self-discovery and does not need to set parameters.
Step 2 Check the monitoring functions of temperature sensor.
Table 8-30 Commissioning the sensor
Check Method
Path: Monitoring > Cabinet >
IT Cabinet n > Cabinet
Collector n
----End
Issue 05 (2019-09-16)
Choose System Settings > Signal Name Modify. The Batch Signal Configuration
page is displayed.
Set Device Type to ECC800, set Device Name to ECC800, and click OK.
On the query result tab page, set the new signal name of AI/DI_2 to Temperature and
click Submit.
Choose Monitoring > System > ECC800 > Running Parameters > AI/DI_2 Port
Settings.
Set Temperature sensor to Enable and click Submit.
Confirm that Temperature sensor type is automatically identified as NTC. Ensure that
Temperature power supply is Yes.
Copyright © Huawei Technologies Co., Ltd.
Normal Connection Status
You can view the current cabinet temperature.
Normal Connection Status
You can view the current cabinet temperature.