Huawei ECC800 User Manual page 79

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
BCB Port
Figure 3-43 BCB port pins
Table 3-63 BCB_1–BCB_4 port pin definitions
Pin
Definition
1
OL
2
STA
3
DRV
4
GND
Table 3-64 BCB_IN and BCB_OUT cascading port pin definitions
Pin
Definition
1
OL
Issue 07 (2020-03-16)
The value of Multi-Hall cur. setting equals the number of positive or negative Hall effect sensors in
a single battery string and should be greater than or equal to 1.
Signal
Description
Monitors whether
the BCB box is
connected
Monitors the
battery circuit
breaker
Controls battery
circuit breaker trip
and outputs 12 V
driving signals
Secondary side
ground
BCB_IN Signal
Description
Specifies whether
the BCB connects
to the signal output
port.
Copyright © Huawei Technologies Co., Ltd.
Status Description
Grounded: BCB
connected.
Disconnected: BCB
not connected.
Grounded: The
battery circuit
breaker is ON.
Disconnected: The
battery circuit
breaker is OFF.
0 V: There is no
driving signal for
BCB tripping.
12 V: There is a
driving signal for
BCB tripping.
BCB_OUT
Status
Signal
Description
Description
Specifies
Grounded
whether the
: BCB
cascaded BCBs
connected
.
connect to the
signal input
Disconne
3 Device Description
Initial Status
Remarks
Disconnected
The four BCBs
can separately
manage tripping
of four battery
routes.
Disconnected
0 V
Initial
Description
Status
Disconnected
Receives
BCB
commands
sent by the
UPS and
70

Advertisement

Table of Contents
loading

Table of Contents