6.1 Linking Alarms with an Alarm Beacon

6.1.1 Linking the Smoke Alarm with the Alarm Beacon

Prerequisites
The alarm beacon is connected to the DO port on the ECC800.
Context
This section describes how to set an alarm linkage by linking output dry contact of the smoke
alarm on the multi-functional sensor to the DO2 port.
After the smoke alarm is linked with the alarm beacon, if smoke is detected inside the smart
module, the alarm beacon connecting to the corresponding DO2 port will generate an audible
and visual alarm.
Procedure
Step 1 Choose System Settings > Alarm Parameter Settings > Alarm Linkage.
Step 2 Select Multi-Func Sensor for Device Type, select Device Type or Device for Linkage type,
and click Confirm.
Step 3 Click Select in the Output Dry Contact list for Smoke alarm. On the Set Dry Contact
Outputs(Multi-Func Sensor) page, set DO2 to Yes and click OK.
Step 4 Click Select in the loudspeaker list for Smoke alarm. On the Please set the
sound(Multi-Func Sensor) page, set loudspeaker to Yes and click OK.
----End
Issue 07 (2020-03-16)
Select Multi-Func Sensor n from the Device Name list if you have selected Device for Linkage type,
and click Confirm.