4.1 WebUI Introduction

4.1.1 Preparations and WebUI Login

Prerequisites
Procedure
Step 1 Connect a network cable between the PC network port and the WAN_1 port (protected by a
security mechanism) on the ECC800.
Table 4-1 Default IP addresses for the WAN and LAN ports on the ECC800
Port
WAN_1
WAN_2
LAN_1 and LAN_2
Step 2 Configure the PC IP address and the WAN_1 IP address in the same network segment.
Issue 07 (2020-03-16)
Operating system: Support Windows 7 and later versions
Browser: IE9 and later versions; Firefox and later versions; Chrome and later versions
The WAN_1 port IP address cannot be set to an IP address in any of the following network
segments: 192.168.0.x, 192.168.8.x, 192.168.248.x, and 192.168.245.x.
IP addresses for the WAN_1 and WAN_2 ports should not be set in the same network
segment.
Copyright © Huawei Technologies Co., Ltd.
4

UI Description

Default IP Address
192.168.1.10
192.168.248.10 (FusionModule800)
192.168.0.10
(FusionModule500/FusionModule1000/FusionModule2
000/FusionModule5000)
192.168.248.10