ECC800 Data Center Controller
User Manual
Indicator
ALM
3G
RF_Z
Table 3-6 PSU indicator description
Indicator
Issue 07 (2020-03-16)
Color
Name
Red
Alarm indicator
Green
3G status
indicator
Green
Communication
status indicator
Color
Name
Green
Power
indicator
Copyright © Huawei Technologies Co., Ltd.
Status
Description
short
with the NetEco (the indicator
intervals
blinks at 4 Hz, on for 0.125s and
then off for 0.125s).
Steady on
A system failure alarm is
generated.
Off
The system is normal.
Steady on
The 3G module is powered on.
Off
The 3G module stops running, or
no 3G module is configured.
Blinking at
The 3G module succeeds in
long
dial-up (the indicator blinks at
intervals
0.5 Hz, on for 1s and then off for
1s).
Blinking at
The 3G module registers with the
short
operator network successfully
intervals
(the indicator blinks at 4 Hz, on
for 0.125s and then off for
0.125s).
Steady on
No network parameters exist, or
a network is to be created.
Blinking at
A network is set up, and no node
long
access is allowed (the indicator
intervals
blinks at 0.5 Hz, on for 1s and
then off for 1s).
Blinking at
A network is set up, and node
super short
access is allowed (the indicator
intervals
blinks at 10 Hz, on for 0.05s and
then off for 0.05s).
Status
Description
Steady on
The converter has a power input.
Off
The converter has no power input or
is faulty.
Blinking at
The converter is being queried (the
long intervals
indicator blinks at 0.5 Hz, on for 1s
and then off for 1s).
Blinking at
The converter application program
short intervals
is being loaded (the indicator blinks
at 4 Hz, on for 0.125s and then off
3 Device Description
17

Advertisement