Huawei ECC800 User Manual page 114

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
Context
Procedure
Step 1 Set the PMAC625 communications address.
1.
2.
3.
Step 2 Add a PMAC625.
Issue 07 (2020-03-16)
The model of the three-phase AC power meter for the PDC is PMAC625.
When connecting devices, you are advised to add devices one by one. If all devices have
been added and powered on, only the BLINK function of the ETH converter can be used
to identify the mapping between the PMAC625 and ETH converter.
Press
on the displayed screen after the PMAC625 is started. Press
entering the programming mode. Modify the password (1 by default) in blinking ones
digit by pressing
Figure 5-7 Programming screen of the PMAC625
Enter the communications address setting screen by pressing
to confirm the setting.
Select the place of the communications address value to be modified by pressing
or
, modify the communications address value (ranging from 1 to 247) by pressing
or
, and then press
Figure 5-8 Communications address of the PMAC625
Copyright © Huawei Technologies Co., Ltd.
or
, and press
to save the setting.
5 Power-On Commissioning
to confirm the setting.
or
after
, and press
105