Huawei ECC800 User Manual page 102

Data center controller
Hide thumbs Also See for ECC800:
Table of Contents

Advertisement

ECC800 Data Center Controller
User Manual
1.
2.
Step 2 Add a NetCol5000-C030.
1.
2.
Table 5-6 Adding a NetCol5000-C030
Path
Choose System
Settings >
Device
Management
and click Add
Device. The
parameters for
adding devices
are displayed.
3.
Step 3 Set the running parameters and control parameters for the NetCol5000-C030 on the WebUI.
1.
2.
Issue 07 (2020-03-16)
Enter the NetCol5000-C030 home page, click Settings, choose the user name Admin
and enter password 000001. After login, the settings screen of the NetCol5000-C030 is
displayed.
Choose Settings > Comm Settings > Modbus Settings, choose Baud rate to 9600 and
set Comm address to 1.
The earlier version has Protocol setting on the screen. The actual screen prevails.
Log in to the ECC800 WebUI as an administrator.
Add a NetCol5000-C030.
Parameter
Name
Device attribute
Device type
Connect to
Communications
port
Device address
Click Test Connect to check whether the NetCol5000-C030 connects to the ECC800
properly.
If the NetCol5000-C030 connects to the ECC800 properly, click Confirm. The
connected devices are displayed in the Number of connected devices list.
If the NetCol5000-C030 does not connect to the ECC800 properly, check whether
the cable between the NetCol5000-C030 and the ECC800 is connected properly,
whether the NetCol5000-C030 and ECC800 are running properly, and whether the
input parameters are consistent with the NetCol5000-C030 parameters.
Log in to the ECC800 WebUI as an administrator.
Choose Monitoring > Air Conditioner > NetCol5000-C0301.
Copyright © Huawei Technologies Co., Ltd.
Setting
Select Air Conditioner from the drop-down list
box.
Select NetCol5000-C030 from the drop-down list
box.
Select ECC800 from the drop-down list box.
Select COM1 from the drop-down list box.
NOTE
The setting example indicates that the NetCol5000-C030
is connected to the COM1 port on the ECC800. If the
NetCol5000-C030 is connected to another port, enter the
number of the connected port.
In this example, Device address is set to 1. During
actual configuration, set the device address for the
NetCol5000-C030 based on the actual situation.
5 Power-On Commissioning
93