ACC Precision Air Conditioner Controller
User Manual
3.2.4 Setting Communications Parameters (IP Settings)
Context
To set communications parameters, log in as the Admin, or Engineer user.
Procedure
Step 1 On the home screen, choose Settings > Comm Settings > IP Settings.
displayed.
Figure 3-5 IP settings
Step 2 Set the parameters by referring to
Table 3-2 IP address settings
Parameter
IP assigning mode
IP address
Subnet mask
Gateway
----End
3.2.5 Setting Communications Parameters (Modbus Settings)
Context
Issue 02 (2016-11-30)
To set communications parameters, log in as the Admin or Engineer user.
If Connection mode is set to Server, a precision air conditioner can be accessed by a
maximum of one element management system (EMS) clients at the same time. If
Connection mode is set to Client, a precision air conditioner can be connected only to
the EMS with the corresponding IP address. If Connection mode is set to Server+client,
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Table
3-2.
Setting Method
Set according to the actual plan.
Set according to the actual plan.
Set according to the actual plan.
Set according to the actual plan.