8.1.6.6 How to Set and Add a PDU8000 (over Modbus RTU)?

Prerequisites
One end of the straight-through cable has been connected to the COM port on the PDU8000,
and the other end has been connected to the COM port on the ECC800-Pro collector or ETH
converter.
Procedure
Step 1 Set the PDU8000 monitoring parameters.
1.
2.
3.
Step 2 Add a PDU8000 (Modbus-RTU).
1.
2.
Table 8-5 Adding a PDU8000
Path
Choose System
Issue 06 (2020-04-22)
Enter the PDU8000 home screen, tap System Info.
Choose System Info > Settings, enter the user name admin and password 000001, and
tap
. In the password message dialog box displayed, tap Confirm.
Tap Communication and check IP address assign to Manual. And set Serial port
baud rate to 9600, and Serial port address to 1 on the displayed communication
settings screen.
Figure 8-10 PDU8000 communication settings screen
Log in to the ECC800-Pro WebUI as an administrator.
Add a PDU8000.
Parameter
Name
Device attribute
Copyright © Huawei Technologies Co., Ltd.
Setting
Select PDU from the drop-down list box.