3.2.9 Setting Teamwork Control Parameters

Prerequisites
To network the chilled water in-room precision air conditioner whose controller software
version is V100R001C20 and chilled water in-room precision air conditioner whose controller
software version is V100R001C00 or V100R001C10 in a teamwork, upgrade the software
version V100R001C00 or V100R001C10 to V100R001C20 first. For details about how to
view the software version of the controller, see
about how to upgrade the software version, see the software upgrade guide.
Assign teamwork group number and teamwork unit address for the teamwork controlled
precision air conditioners as follows:
Issue Draft A (2014-12-26)
Teamwork group no.: Group the precision air conditioners in adjacent areas as one, that
is, assign one teamwork control number for them. At most four teamwork control groups
can be assigned (1–4).
Teamwork unit address: The address for the precision air conditioner in the same group
cannot be the same (address range: 1–32). The precision air conditioner addressed 1 is
the master one that collects, processes, and delivers data. Set the unit address numbers
from one to the Total number of units in this group. If the address of a device exceeds
the range, the device cannot enter the teamwork control. If the address of any unit amid
the range is unavailable, the teamwork topology shows that this device is offline.