Mitsubishi Electric 800 Series Instruction Manual page 381

600v class specification inverter
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

(M) Monitor display and monitor output signal
Output frequency detection (FU (FB) signal, FU2 (FB2) signal, FU3 (FB3)
signal, Pr.42, Pr.43, Pr.50, Pr.116)
• Output frequency detection (FU (FB)) is output when the output frequency reaches the Pr.42 setting or higher.
• The FU (FU2, FU3) signals can be used for electromagnetic brake operation, opening, etc.
• The FU (FU2, FU3) signal is output when the output frequency (frequency command) reaches the set frequency. The FB
(FU2, FU3) signal is output when the actual rotation detection speed (estimated speed in Real sensorless vector control,
feedback value in vector control) of the motor reaches the set frequency. The FU signal and FB signal are output in the
same manner under V/F control, Advanced magnetic flux vector control and encoder feedback control.
• Frequency detection that is dedicated to reverse rotation can be set by setting the detection frequency in Pr.43. This is
useful for changing the timing of the electromagnetic brake operation during forward rotation (lifting) and reverse rotation
(lowering) in operations such as lift operation.
• When Pr.43 ≠ "9999", forward rotation uses the Pr.42 setting and reverse rotation uses the Pr.43 setting.
• When outputting a frequency detection signal separately from the FU signal, set the detection frequency in Pr.50 or Pr.116.
When the output frequency reaches the Pr.50 setting or higher, the FU2 (FB2) signal is output (when it reaches the Pr.116
setting or higher, the FU3 (FB3) signal is output).
Forward
rotation
(Hz)
Output
signal
FU/FB
OFF
FU2/FB2
OFF
FU3/FB3
OFF
• For each signal, refer to the following table and assign the function by Pr.190 to Pr.196 (Output terminal function
selection).
Pr.190 to Pr.196 settings
Output
signal
Positive logic
FU
4
FB
41
FU2
5
FB2
42
FU3
6
FB3
43
380
PARAMETERS
Pr.116
Pr.50
Pr.42
Reverse
rotation
ON
OFF
ON
OFF
ON
OFF
Negative logic
104
42, 43
141
105
50
142
106
116
143
Pr.43
Time
Pr.50
Pr.116
ON
OFF
ON
OFF
ON
OFF
Pr.