Control method
Setting the motor capacity and the number of motor poles (Pr.80, Pr.81)
• Motor specifications (the motor capacity and the number of motor poles) must be set to select Advanced magnetic flux
vector control, Real sensorless vector control or vector control.
• Set the motor capacity (kW) in Pr.80 Motor capacity and set the number of motor poles in Pr.81 Number of motor poles.
NOTE
• Setting the number of motor poles in Pr.81 changes the Pr.144 Speed setting switchover setting automatically. (Refer to
page
345.)
Selection of control method and control mode
• Select the inverter control method from V/F control, Advanced magnetic flux vector control (speed control), Real sensorless
vector control (speed control, torque control), vector control (speed control, torque control, and position control), and PM
sensorless vector control (speed control, position control).
Pr.80
Pr.800
(Pr.453)
Pr.71
,
setting
Pr.81
(Pr.450)
value
(Pr.454)
0, 100
1, 101
2, 102
3, 103
4, 104
5, 105
Induction
6, 106
motor
9, 109
10, 110
11, 111
Other
than 9999
12, 112
9999

20 (initial
value)
9, 109
20 (initial
value),
110
IPM/SPM
motor
0 to 6, 100 to 106
13, 14, 113, 114

The setting values of 100 and above are used when the fast-response operation is selected.

Advanced magnetic flux vector control if a vector control compatible option is not installed.

The operation for the setting of "20 or 110" is performed when a value other than "9 or 109" is set.

The operation for the setting of "20 or 110" is performed when a value other than "9999" is set.

V/F control when Pr.80 or Pr.81 is "9999", regardless of the Pr.800 setting.
138
PARAMETERS
Pr.451
setting
Control method
value


Vector control
Vector control test operation
Real sensorless vector
control
Advanced magnetic flux
20
vector control
9999
(initial
Advanced magnetic flux vector control for the second motor
value)
PM sensorless vector control test operation
PM sensorless vector
20, 110

control

Vector control (Refer to the instruction manual of the FR-A8APR.)
9999
The setting value of Pr.800 is used for the second motor.
(initial
(PM sensorless vector control (speed control) when Pr.800="9 or 109")
value)
V/F control
For manufacturer setting. Do not set.
Control mode
Speed control
Torque control
Speed control/torque
control switchover
Position control

Speed control/position
control switchover
Position control/torque
control switchover
Torque control (variable-
current limiter control)
Speed control
Torque control
Speed control/torque
control switchover
Speed control
Speed control
Remarks
MC signal ON: torque control
MC signal OFF: speed control
MC signal ON: position control
MC signal OFF: speed control
MC signal ON: torque control
MC signal OFF: position control
MC signal ON: torque control
MC signal OFF: speed control