• To switch between the Network operation mode and the External operation mode
1) Set Pr.79="0" (initial value) or "2, "6" or "7". (When Pr.79 ="7" and the X12 (MRS) signal is ON, the operation mode can
be switched.)
2) Set Pr.340 Communication startup mode selection ="0" (initial value), "1" or "2".
3) Set "66" in one of Pr.178 to Pr.189 to assign the NET-External operation switching signal (X66) to a terminal.
4) When the X66 signal is ON, Network operation mode is selected. When the X66 signal is OFF, the External operation
mode is selected.
Pr.340
Pr.79
setting
setting
0 (initial value)
1
2
3, 4
0
(initial value),
6
1, 2
X12 (MRS)
ON
7
X12 (MRS)
OFF

When "Pr.550 NET mode operation command source selection = "0" (communication option control source)" and no communication option is
connected, the External operation mode is selected.

When the X16 signal is OFF, the PU operation mode is selected. Also, when the X65 signal is assigned, the operation mode follows the ON/OFF
state of the X65 signal.
NOTE
• The priority of Pr.79 and Pr.340 and signals is Pr.79 > X12 > X66 > X65 > X16 > Pr.340.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
???????
Pr.15 Jog frequency
page 312
Pr.4 to Pr.6, Pr.24 to 27, Pr.232 to Pr.239 multi-speed operation
Pr.75 Reset selection/disconnected PU detection/PU stop selection
Pr.178 to Pr.182 (Input terminal function selection)
Pr.190 to Pr.196 (Output terminal function selection)
Pr.340 Communication startup mode selection
Pr.550 NET mode operation command source selection
(D) Operation command and frequency command
X66 signal state
ON (NET)
OFF (External)
NET operation mode
External operation mode

PU operation mode
NET operation mode
External operation mode

External/PU combined operation mode
NET operation mode
External operation mode

NET operation mode
External operation mode

External operation mode
page 314
page 244
page 415
page 370
page 300
page 301
REMARKS

PU operation mode fixed
Switching to PU operation mode is disabled.
External/PU combined operation mode fixed
Switching between operation modes is

enabled while running.
Output is shutoff in the External operation

mode.
The operation mode is forcibly switched to the
External operation mode.
PARAMETERS
5
GROUP
D
299