Mitsubishi Electric 800 Series Instruction Manual page 469

600v class specification inverter
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

(A) Application parameters
NOTE
• When the current averaging range includes the constant-output range, the output current may become large in the constant-
output range.
• When the average current value in the current averaging range is small, deceleration time becomes longer as the output
frequency increases.
• The automatic restart after instantaneous power failure function, fast-response current limit operation, fast-response current
limit operation, shortest acceleration/deceleration, and optimum acceleration/deceleration are invalid.
• Changing the terminal assignment with Pr.178 to Pr.189 (Input terminal function selection) may affect other functions. Set
parameters after confirming the function of each terminal.
• Under the following operating conditions, the load torque high-speed frequency function is invalid:
PU operation (Pr.79), PU + External operation (Pr.79), JOG operation, PID control function operation (Pr.128), remote setting
function operation (Pr.59), orientation control function operation, multi-speed setting (RH, RM, RL signal), torque control,
position control.
• When the average current during acceleration is too small, it may be judged as regeneration, and the maximum frequency
may become the setting of Pr.5.
• The output frequency may change due to the load, so do not get unnecessarily close to the motor or machine.
Parameters referred to
???????
Pr.4 to Pr.6, Pr.24 to Pr.27 (Multi-speed setting)
Pr.57 Restart coasting time
Pr.59 Remote function selection
Pr.79 Operation mode selection
Pr.128 PID action selection
Pr.178 to Pr.189 (Input terminal function selection)
468
PARAMETERS
page 314
page 515
page 279
page 291
page 488
page 415