Adjusting the output terminal response level (Pr.289)
• The response level of the output terminals can be delayed in a range of 5 to 50 ms. (Operation example for the RUN
signal.)
RUN
Pr.289 = 9999
RUN
Pr.289 ≠ 9999
Pr.289
NOTE
• When Pr.157 OL signal output timer is set for the Overload warning (OL) signal output, the OL signal is output when the set
time of (Pr.157 + Pr.289) elapses.
• For the output signal and the fault code output (on
invalid (no filter).
Inverter operation ready signals (RY, RY2 signals) and inverter running
signals (RUN, RUN2, RUN3 signals)
 Operation under V/F control and
Advanced magnetic flux vector control
Power
ON
supply
ON
STF
RH
Pr. 13
Reset
processing
ON
RY
RUN
(RUN2)
ON
RUN3
• According to the inverter condition, the ON/OFF operation of each signal is as shown below.
Start signal
Output
OFF
signal
(during
stop)
RY
ON

RY2
OFF
RUN
OFF
RUN2
OFF
RUN3
OFF

OFF during power failure or undervoltage.

Output is shutoff in conditions like a fault and when the MRS signal is ON.

OFF while power is not supplied to the main circuit power supply.
OFF
ON
ON
OFF
Pr.289
OFF
OFF
ON
DC injection brake
operation point
DC injection
brake
operation
Time
OFF
ON
OFF
OFF
Start signal
Start
ON
signal ON
(during
(running)
stop)
ON
ON
OFF
OFF
OFF
ON
OFF
ON
ON
ON
(M) Monitor display and monitor output signal
Time
page
386) used in the PLC function (on
• When the inverter is ready for operation, the Inverter
operation ready (RY) signal turns ON (stays ON during
operation.)
• When the inverter output frequency reaches Pr.13
Starting frequency or higher, the Inverter running (RUN,
RUN2) signals turn ON. The signal is OFF while the
inverter is stopped and during DC injection brake
operation.
• The Inverter running and start command is ON (RUN3)
signal is ON while the inverter is running or the start
signal is ON. (When the start command is ON, the RUN3
signal output turns ON even while the inverter's
protective function is activated or the MRS is ON.)
During DC injection brake operation as well, the output is
ON, and when the inverter stops, it turns OFF.
Output shutoff
DC
injection
brake
Start
Start
operation
signal
signal
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF
page
531), the Pr.289 setting is
Automatic restart after
instantaneous power failure

Coasting
Start
Start
Restarting
signal
signal
ON
OFF
ON
ON

OFF
ON
OFF
ON
OFF
ON
ON
OFF
ON
PARAMETERS
5
GROUP
M
375