Analog Input Selection - Mitsubishi Electric 800 Series Instruction Manual

600v class specification inverter
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

5.12.1

Analog input selection

The functions to switch the analog input terminal specifications, override function, forward/reverse rotation by the input
signal polarity are selectable.
Pr.
Name
73
Analog input selection
T000
267
Terminal 4 input
T001
selection
Analog input specification selection
• Concerning the terminals 2 and 4 used for analog input, the voltage input (0 to 5 V, 0 to 10 V) and current input (0 to 20 mA)
are selectable. To change the input specification, change the parameters (Pr.73, Pr.267) and voltage/current input switch
settings (switches 1, 2).
Voltage/current
input switch
Switch 2
Switch 1
2
4
Switch state
Input specification
ON
Current input
Switch 1
OFF
Voltage input (initial status)
ON
Current input (initial status)
Switch 2
OFF
Voltage input
• Change the setting of the voltage/current input selection switch to change the rated specification of terminal 2 or 4.
• Correctly set Pr.73, Pr.267 and voltage/current input switch settings so that the analog signal appropriate for the settings is
input. The incorrect settings shown in the table below cause a failure. Other incorrect settings result in an incorrect
operation.
Setting causing a failure
Terminal
Switch setting
input
ON (current input)
Voltage input
OFF (voltage input)
Current input
NOTE
• Check the voltage/current input switch number indication before setting, because it is different from the FR-A700 series
switch number indication.
(T) Multi-Function Input Terminal Parameters
Setting
Initial value
range
0 to 5, 10
to 15
1
6, 7, 16, 17
0
0
1
2
Switch 1: Terminal 2 input
ON: Current input
OFF: Voltage input (initial status)
Switch 2: Terminal 4 input
ON: Current input (initial status)
OFF: Voltage input
Input
terminal
For voltage input, the input resistance is 10±1 kΩ and the
Terminal 2
maximum permissible voltage is 20 VDC.
For current input, the input resistance is 245±5 Ω and the
Terminal 4
maximum permissible current is 30 mA.
Causes an analog signal output circuit failure in an external device
(due to increased loads on the signal output circuit of the external device).
Causes an input circuit failure in the inverter
(due to an increased output power in the analog signal output circuit of an external device).
The terminal 2 input specification (0 to 5
Switch 1 - OFF
V, 0 to 10 V, 0 to 20 mA) and terminal 1
(initial status)
input specification (0 to ±5 V, 0 to ±10
V) are selectable.
Also the override and reversible
Switch 1 - ON
operation settings are selectable.
Switch 2 - ON
Terminal 4 input, 4 to 20 mA
(initial status)
Terminal 4 input, 0 to 5 V
Switch 2 - OFF
Terminal 4 input, 0 to 10 V
Rated specification
Operation
PARAMETERS
Description
GROUP
T
393
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents