Start of sampling and copying of data (Pr.1020, Pr.1024)
• Set the trace operation. The trace operation is set by setting Pr.1020 Trace operation selection.
• When "1" is set in Pr.1020, sampling is started.
• When "2" is set in Pr.1020, a trigger is regarded as having been generated (for instance, a forced trigger), sampling is
stopped and the trace is started.
• When "3" is set in Pr.1020, sampling is stopped.
• When "4" is set in Pr.1020, the trace data in internal RAM is transferred to a USB memory device. (Trace data cannot be
transferred during sampling.)
• To automatically start sampling when the power supply is turned ON or at a recovery after an inverter reset, set "1" to
Pr.1024 Sampling auto start.
Pr.1020
setting
0
Sampling standby
1
Sampling start
2
Forced trigger (sampling stop)
3
Sampling stop
4
Data transmission
Selection of trace operation by input terminal (TRG signal, TRC signal)
• Trace operation can be selected by signal inputs.
• A forced trigger can be applied when the Trace trigger input (TRG) signal is ON.
• Sampling is started and stopped by the Trace sampling start/end (TRC) signal turning ON and OFF, respectively.
• To input the TRG signal, set "46" in any of Pr.178 to Pr.189 (Input terminal function selection), and to input the TRC
signal, set "47" to assign the function to a terminal.
NOTE
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Operation
(A) Application parameters
PARAMETERS
5
GROUP
A
539