Mitsubishi Electric 800 Series Instruction Manual page 546

600v class specification inverter
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

How to wire RS-485 terminals
• 1 inverter and 1 computer with RS-485 terminals
• Multiple inverters and 1 computer with RS-485 terminals
Computer
RDA
RDB
SDA
SDB
RSA
RSB
CSA
CSB
SG
FG

Make connection in accordance with the Instruction Manual of the computer to be used with.
Fully check the terminal numbers of the computer since they vary with the model.

For the inverter farthest from the computer, set the terminating resistor switch to ON (100  side).
NOTE
• For branching, connect the wires as shown below.
VCC
To computer ground
To computer receive
To computer send
Two-wire type connection
• If the computer is 2-wire type, a connection from the inverter can be changed to 2-wire type by passing wires across
reception terminals and transmission terminals of the RS-485 terminals.
NOTE
• A program should be created so that transmission is disabled (receiving state) when the computer is not sending and
reception is disabled (sending state) during sending to prevent the computer from receiving its own data.
Computer
RDA
RDB
SDA
SDB
RSA
RSB
∗1
CSA
CSB
SG
FG
∗1
SG
SG
Station 0
TXD RXD
VCC
Computer
Transmission
enable
Reception
enable
SG
(N) Operation via communication and its settings
∗2
SG
SG
SG
Station 1
TXD RXD
To receiving terminal
of the next inverter
To sending terminal
of the next inverter
To next inverter
To earth (ground)
terminal
Inverter
TXD+
TXD-
RXD+
RXD-
Pass a wire
SG
∗2
SG
Station n
545
PARAMETERS
5
GROUP
N

Hide quick links:

Advertisement

Table of Contents
loading