Droop Control - Mitsubishi Electric 800 Series Instruction Manual

600v class specification inverter
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

5.16.15

Droop control

This is a function to give droop characteristics to the speed by balancing the load in proportion with the load torque
during the Advanced magnetic flux vector control, Real sensorless vector control, vector control, and PM sensorless
vector control.
This is effective when balancing the load when using multiple inverters.
Pr.
Name
286
Droop gain
G400
287
Droop filter time
G401
constant
288
Droop function
G402
activation selection
994
Droop break point gain
G403
995
Droop break point torque
G404
679
Second droop gain
G420
680
Second droop filter time
G421
constant
681
Second droop function
G422
activation selection
682
Second droop break
G423
point gain
683
Second droop break
G424
point torque
Magnetic flux
Magnetic flux
Magnetic flux Sensorless
Sensorless
Sensorless Vector
Initial
Setting
value
range
0
0%
0.1% to 100%
0.3 s
0 to 1 s
0
1
2
10
0
11
20
21
22
0.1 to 100%
9999
9999
100%
0.1 to 100%
0 to 100%
9999
9999
0 to 1 s
9999
9999
0, 1, 2, 10, 11,
20, 21, 22
9999
9999
0.1 to 100%
9999
9999
0.1 to 100%
9999
9999
(G) Control parameters
Vector
Vector
PM
PM
PM
Description
Normal operation
Droop control enabled
Set the droop amount at the time of rated torque as % value
of the rated motor frequency.
Set the filter time constant to apply to the current for torque.
Without droop control during
acceleration/deceleration
(With 0 limit)
Continuous droop control
during operation
(With 0 limit)
Continuous droop control
during operation
(Without 0 limit)
Without droop control during
acceleration/deceleration
(With 0 limit)
Continuous droop control
during operation
(With 0 limit)
No droop control during
acceleration/deceleration
(with 0 limit)
Continuous droop control
during operation (with 0 limit)
Continuous droop control
during operation
(without 0 limit)
No droop control during
acceleration/deceleration
(with 0 limit)
No function
Set the torque when the droop amount is to be changed.
Refer to Pr.286
The first droop control setting
is applied to the operation.
Refer to Pr.287
The first droop control setting
is applied to the operation.
Refer to Pr.288
The first droop control setting
is applied to the operation.
Refer to Pr.994
The first droop control setting
is applied to the operation.
Refer to Pr.995
The first droop control setting
is applied to the operation.
PARAMETERS
Rated motor frequency is
the droop compensation
reference
Motor speed is the droop
compensation reference
The Pr.1121 setting is the
droop compensation
reference.
The Pr.1121 setting is the
droop compensation
reference.
Set the second droop
control.
The droop control is
enabled when the RT
signal is ON.
GROUP
G
621
5