Mitsubishi Electric 800 Series Instruction Manual page 459

600v class specification inverter
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

(A) Application parameters
Pr.
Name
642
Second brake opening
A120
frequency
643
Second brake opening
A121
current
644
Second brake opening
A122
current detection time
645
Second brake operation
A123
time at start
646
Second brake operation
A124
frequency
647
Second brake operation
A125
time at stop
648
Second deceleration
A126
detection function selection
650
Second brake opening
A128
current selection
651
Second brake operation
A129
frequency selection

The speed deviation excess detection frequency when vector control compatible option is mounted during vector control. (For the details, refer
to
page
179.)
Connection diagram
Sink logic
Pr.184 = 15
Pr.190 = 20
Power
supply
Multi-speed signal
Brake opening completion signal
NOTE
• The automatic restart after instantaneous power failure function and orientation function do not operate when brake
sequence is selected.
• To use this function, set the acceleration/deceleration time to 1 s or higher.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) and Pr.190 to Pr.196
(Output terminal function selection) may affect the other functions. Set parameters after confirming the function of each
terminal.
458
PARAMETERS
Initial
value
3 Hz
130%
0.3 s
0.3 s
6 Hz
0.3 s
0
0
0
MC
MCCB
R/L1
S/L2
T/L3
Start signal
STF
RH
RUN(BOF)
AU(BRI) ∗
(BRI)
SD
Setting
range
0 to 30 Hz
Refer to Pr.278.
0 to 400%
Refer to Pr.279.
0 to 2 s
Refer to Pr.280.
0 to 5 s
Refer to Pr.281.
0 to 30 Hz
Refer to Pr.282.
0 to 5 s
Refer to Pr.283.
0, 1
Refer to Pr.284.
0, 1
Refer to Pr.639.
0, 1
Refer to Pr.640.
Mechanical
brake
U
V
Motor
W
24VDC
∗3
MC
∗2
Brake opening request
signal (BOF)
1
SE
Description
Set the second brake sequence
function.
The second brake sequence function
is enabled when the RT signal is ON.

The input signal
terminals differ by the
settings of Pr.178 to
Pr.189.

The output signal
terminals differ by the
settings of Pr.190 to
Pr.196.