Changing The Display Increment Of The Numerical Values Used In Pid Control - Mitsubishi Electric 800 Series Instruction Manual

600v class specification inverter
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

Parameters referred to
Pr.59 Remote function selection
Pr.73 Analog input selection
page 393
Pr.79 Operation mode selection
Pr.178 to Pr.189 (Input terminal function selection)
Pr.190 to Pr.196 (Output terminal function selection)
Pr.290 Monitor negative output selection
C2 (Pr.902) to C7 (Pr.905) Frequency setting voltage (current) bias/gain
5.14.11
Changing the display increment of the
numerical values used in PID control
When the operation panel or the parameter unit is used, the display unit of parameters and monitored items related to
PID control can be changed to various units.
Pr.
Name
759
Operation mode
A600
selection
934
PID display bias
A630
coefficient
934
PID display bias analog
A631
value
935
PID display gain
A632
coefficient
935
PID display gain analog
A633
value
1136
Second PID display bias
A670
coefficient
1137
Second PID display bias
A671
analog value
1138
Second PID display gain
A672
coefficient
1139
Second PID display gain
A673
analog value
1142
Second PID unit
A640
selection
page 279
page 291
page 415
page 370
page 357
Initial
Setting range
value
0 to 43
0
9999
0 to 500
9999
9999
20%
0 to 300%
0 to 500
9999
9999
100%
0 to 300%
0 to 500
9999
9999
20%
0 to 300%
0 to 500
9999
9999
100%
0 to 300%
9999
0 to 43, 9999
(A) Application parameters
page 402
Description
Change the PID control-related display unit that is displayed
on the operation panel or the parameter unit.
Without display unit switching
Set the coefficient of the bias side (minimum) of measured
value input.
Displayed in %.
Set the converted % of the bias side (minimum) current/
voltage of measured value input.
Set the coefficient of the gain side (maximum) of measured
value input.
Displayed in %.
Set the converted % of the gain side (maximum) current/
voltage of measured value input.
Refer to Pr.934
Refer to Pr.934
Refer to Pr.935
Second PID control
Refer to Pr.935
Refer to Pr.759
501
PARAMETERS
5
GROUP
A