Mitsubishi Electric 800 Series Instruction Manual page 451

600v class specification inverter
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

(A) Application parameters

Be careful of the capacity of the sequence output terminals.
The applied terminals differ by the settings of Pr.190 to Pr.196 (Output terminal function selection).
Open collector output of inverter (RUN, SU, IPF, OL, FU) 24 VDC 0.1 A
Inverter relay output (A1-C1, B1-C1, A2-B2, B2-C2)
Relay output option (FR-A8AR)

When connecting a DC power supply, insert a protective diode.
When connecting an AC power supply, use the relay output option (FR-A8AR) and use contact outputs.

The applied terminals differ by the settings of Pr.180 to Pr.189 (Input terminal function selection).

To use the signal, assign the function to the output terminal Pr.190 to Pr.195 (Output terminal function selection) of the converter unit. Always
set the negative logic for the ALM signal.
NOTE
• Use the electronic bypass function in External operation mode. In addition, the wiring terminals R1/L11 and S1/L21 must be
connected to a separate power source that does go through MC1. Be sure to connect using a separate power supply.
• Be sure to provide a mechanical interlock for MC2 and MC3.
• Operation of magnetic contactor (MC1, MC2, MC3)
Magnetic
Installation location
contactor
Between power supply and inverter
MC1
input side
MC2
Between power supply and motor
MC3
Between inverter output side and motor
• The input signals are as shown below.
Applied
Signal
terminal
MRS
MRS

CS
CS
STF
STF
(STR)
(STR)
Set one of Pr.180
OH
to Pr.189 to "7".
RES
RES
Set "95" and "96"
X95/X96
in any of Pr.180
to Pr.189.

For separated converter types, the X10 signal is assigned to the terminal MRS in the initial setting. For the MRS signal, set "24" to any of
Pr.180 to Pr.189 (Input terminal function selection) to assign the function to another terminal.

When the MRS signal is OFF, neither the commercial power supply operation nor the inverter operation can be performed.

The CS signal operates only when the MRS signal is ON.

STF (STR) operates only when the MRS and CS signals are both ON.

The RES signal can be used for reset input acceptance with Pr.75 Reset selection/disconnected PU detection/PU stop selection. When
RES signal and another input signal are simultaneously input, the MC operation by the RES signal has a higher priority.

MC1 turns OFF at an inverter fault.

When Pr.138="0 (electronic bypass invalid at a fault)", MC2 is OFF. When Pr.138="1 (electronic bypass valid at a fault)", MC2 is ON.

MC operation
: MC-ON
: MC-OFF
-: During inverter operation, MC2-OFF, MC3-ON
During commercial power supply operation, MC2-ON, MC3-OFF
Invariance: The status before changing the signal ON or OFF is held.
450
PARAMETERS
Output terminal capacity
power supply operation
Shorted
Shorted
Open
Function
Selects whether or not
operation is available.

Inverter/commercial power
supply operation switchover
Inverter operation command
(Disabled during commercial
power supply operation)

External thermal relay input
Operation status reset

Converter unit fault /
Converter unit fault (E.OHT,
E.CPU)
Output terminal permissible load
230 VAC 0.3 A
30 VDC 0.3 A
During commercial
During inverter
Shorted
Open
Shorted
Operation
ON Electronic bypass operation
available
OFF Electronic bypass operation
not available
ON Inverter operation
OFF Commercial power supply

operation
ON Forward rotation (reverse
rotation)
OFF Stop
ON Motor normal
OFF Motor fault
ON Reset
OFF Normal operation
X95 signal OFF, X96 signal OFF
Converter fault (E.OHT, E.CPU)
X95 signal ON, X96 signal ON
Converter normal
X95 signal OFF, X96 signal ON
Converter fault (other than E.OHT
or E.CPU)
Operation
During inverter fault
operation
Open
(short by reset)
Open
(Selected by Pr.138. Always
open when the external
thermal relay is operating.)
Open
MC operation
MC1
MC2

-
-
Unchanged
-
-
-


MC3
-
Unchanged
-
Unchanged
-
-

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents