Errors (Alarms); Error (Alarm) Definitions - Mitsubishi Electric FR-A520-2.2K Instruction Manual

Transistorized inverter, high function & low acoustic noise
Hide thumbs Also See for FR-A520-2.2K:
Table of Contents

Advertisement

5.1 Errors (Alarms)

5 PROTECTIVE FUNCTIONS
5.1 Errors (alarms)
If any fault has occurred in the inverter, the corresponding protective function is activated and the error
(alarm) indication appears automatically on the PU display. When the protective function is activated, refer to
"5.2 Troubleshooting" and clear up the cause by taking proper action. If an alarm stop has occurred, the
inverter must be reset to restart it.

5.1.1 Error (alarm) definitions

Operation
Parameter
Panel
Unit
Display
(FR-PU04)
(FR-DU04)
OC During
During
E.OC1
Acc
acceleration
During
Stedy Spd
E.OC2
constant
OC
speed
During
OC During
E.OC3
deceleration
Dec
During stop
OV During
During
E.OV1
Acc
acceleration
During
Stedy Spd
E.OV2
constant
OV
speed
During
OV During
E.OV3
deceleration
Dec
During stop
Motor
E.THM
Overload
Ovrload
shut-off
(electronic
overcurrent
protection)
Inv.
E.THT
Overload
Inst.Pwr.
Instantaneous power failure
E.IPF
Loss
protection
Under
E.UVT
Undervoltage protection
Voltage
H/Sink
E.FIN
Fin overheat
O/Temp
Fan
FN
Fan fault
Failure
Br.Cct.
Brake transistor alarm
E. BE
Fault
detection
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Name
When the inverter output current reaches or exceeds approximately
Overcurrent
200% of the rated current, the protective circuit is activated to stop the
shut-off
inverter output.
If regenerative energy from the running motor causes the inverter's
Regenerative
internal main circuit DC voltage to reach or exceed the specified value,
overvoltage
the protective circuit is activated to stop the inverter output.
shut-off
This may also be activated by a surge voltage generated in the power
supply system.
The electronic overcurrent protection in the inverter detects motor
overheat due to overload or cooling capability reduced during constant-
speed operation. When 85% of the preset value is reached, pre-alarm
(TH indication) occurs. When the specified value is reached, the
Motor
protective circuit is activated to stop the inverter output. When a special
motor such as a multi-pole motor or more than one motor is run, the
motor cannot be protected by the electronic overcurrent protection.
Provide a thermal relay in the inverter output circuit.
If a current more than 150% of the rated output current flows and
overcurrent shut-off (OC) does not occur (200% or less), inverse-time
Inverter
characteristics cause the electronic overcurrent protection to be activated
to stop the inverter output. (Overload immunity: 150%, 60 seconds)
If a power failure has occurred in excess of 15ms (this applies also to
inverter input shut-off), this function is activated to stop the inverter
output to prevent the control circuit from misoperation. At this time, the
alarm output contacts are opened (across B-C) and closed (across A-C)
(Note 1). If a power failure persists for more than 100ms, the alarm
output is not provided, if the start signal is on at the time of power
restoration, the inverter will restart. (If a power failure is instantaneous
within 15ms, the control circuit operates properly.)
•If the inverter power supply voltage reduces, the control circuit will not
operate properly, resulting in decreased motor torque or increased
heat generation. To prevent this, if the power supply voltage reduces
below 150V (about 300V for the 400V class), this function stops the
inverter output.
•When a jumper is not connected across P-P1 〈+ -P1〉, the undervoltage
protective function is activated.
If the cooling fin overheats, the temperature sensor is activated to stop
the inverter output.
For the inverter which contains a cooling fan, FN is displayed on the
operation panel and the fan fault signal (FAN) and light fault signal (LF)
are output when the cooling fan stops due to a fault or operates
differently from the setting of Pr. 244 "cooling fan operation selection".
If the brake circuit fault has occurred due to damaged brake transistors,
etc., this function stops the inverter output.
In this case, the inverter power must be switched off immediately.
174
PROTECTIVE FUNCTIONS
Description

Advertisement

Table of Contents
loading

Table of Contents