(C) Motor constant parameters
NOTE
• Even if the start signal is turned ON during zero speed control or servo lock, tuning is performed at startup.
• The Y39 signal remains ON as long as there is second flux even after the motor is stopped.
• The X28 signal is disabled while the Y39 signal is ON.
• The STF and STR signals are enabled after completing tuning at start.
• The Inverter running (RUN) signal is not turned ON during online auto tuning. The RUN signal is turned ON after starting up.
• It is disabled during V/F control or PM sensorless vector control.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) and Pr.190 to Pr.196
(Output terminal function selection) may affect other functions. Set parameters after confirming the function of each
terminal.
Magnetic flux observer (tuning always) (setting value "2")
• If vector control is performed using a motor with an encoder, this setting improves torque accuracy.
Estimate or measure the flux within the motor using the current running through the motor and the inverter output voltage.
Because the flux of a motor can always be accurately estimated (even during operation), fine characteristics can always be
attained without being affected by temperature change in the second resistance.
• When vector control (Pr.80, Pr.81 or Pr.800) is used, select the magnetic flux observer. (Refer to
• Make sure to perform offline auto tuning before performing online auto tuning.
Tuning the second applied motor (Pr.574)
• When switching two different motors by one inverter, set the second motor in Pr.450 Second applied motor. (In the initial
setting, no second motor is applied. (Refer to
Pr.574 is enabled when the Second function selection (RT) signal is turned ON.
Pr.
450
Applicable motor
453
Motor capacity (with the rated motor current equal to or lower than the inverter rated current)
454
Number of motor poles

If a motor with substantially low rated current compared with the inverter rated current is used, speed and torque accuracies may deteriorate due
to torque ripples, etc. Set the rated motor current to about 40% or higher of the inverter rated current.
NOTE
• The RT signal is a second function selection signal. The RT signal also enables other second functions. (Refer to
The RT signal is assigned to the terminal RT in the initial status. Set "3" in any of Pr.178 to Pr.189 (Input terminal function
selection) to assign the RT signal to another terminal.
• Changing the terminal assignment using Pr.178 to Pr.189 (Input terminal function selection) may affect the other
functions. Set parameters after confirming the function of each terminal.
Parameters referred to
???????
Pr.9 Electronic thermal O/L relay
Pr.71 Applied motor
page 423
Pr.80 Motor capacity
page
Pr.81 Number of motor poles
Pr.96 Auto tuning setting/status
Pr.178 to Pr.189 (Input terminal function selection)
Pr.190 to Pr.196 (Output terminal function selection)
Pr.800 Control method selection
5.13.5

Signal loss detection of encoder signals

V/F
V/F
V/F
If encoder signals are disconnected during encoder feedback control, orientation control or vector control, Signal loss
detection (E.ECT) is turned ON to shut off the inverter output.
Pr.
376
855
Encoder signal loss detection
C148
C248
enable/disable selection



The setting is available when a Vector control compatible plug-in option is installed.

These parameters are available when the control terminal option (FR-A8TP) is installed.
446
PARAMETERS
page
Description
page 317
137,
page
426,
page 436
page
137,
page
426,
page 436
page
426,
page 436
page 415
page 370
page 137
Magnetic flux Vector
Magnetic flux
Magnetic flux
Vector
Vector
Name
423.))
Initial value
Setting range
0
0
1
page
137.)

page
Description
Signal loss detection disabled
Signal loss detection enabled
415.)