LMV36...
AGM60...
General
22/248
Building Technologies Division
Infrastructure & Citiies Sector
1.8
Standards and certificates
Conformity to EEC directives
- Electromagnetic compatibility EMC (immunity)
- Directive for gas-fired appliances
- Low-voltage directive
- Pressure equipment directive
ISO 9001: 2008
ISO 14001: 2004
Cert. 00739
Cert. 38233
Test specifications:
EN 230, EN 298, EN 1643, EN 12067-2, EN 13611
1.9
Service notes
If fuses are blown, the unit must be returned to Siemens (refer to chapter
Warning notes)
Error diagnostics can only be made via the LMV36... (BCI)
1.10 Life cycle
The burner management system LMV36... has a designed lifetime* of 250,000 burner
startup cycles which, under normal operating conditions in heating mode, correspond to
approx. 10 years of usage (starting from the production date given on the type field).
The AGM60... switch unit has a designed lifetime* of 5,000 burner startup cycles which,
under normal operating conditions in heating mode, correspond to approx.
10 years of usage (starting from the production date given on the type field).
This lifetime is based on the endurance tests specified in standard EN 230 / EN 298.
A summary of the conditions has been published by the European
Manufacturers Association
The designed lifetime is based on use of the LMV36... / AGM60... according to the
manufacturer's Basic Documentation. When reaching the designed lifetime in terms of
the number of burner startup cycles or time of usage, the LMV36... / AGM60... must be
replaced by authorized personnel.
* The designed lifetime is not the warranty time specified in the Terms of Delivery
1.11 Disposal notes
The unit contains electrical and electronic components and must not be disposed of
together with domestic waste. Local and currently valid legislation must be observe
Basic documentation LMV36...
1 Safety notes
(Afecor) (www.afecor.org).
2004/108/EC
2009/142/EC
2006/95/EC
97/23/EC
Control
CC1P7544en
25.09.2013