23.5

Timeout for menu operation

158/248
Building Technologies Division
Infrastructure & Citiies Sector
The time for automatically leaving the parameter setting level can be adjusted between
10 and 120 minutes, using the following parameter:
No.
Parameter
127
Timeout for menu operation
If, during that period of time, there is no operation via the AZL2..., the parameter setting
level is quit and the password level reset to Info / Service.
Caution!
In addition, this timeout or interruption of communication between LMV36... and
the AZL2... during the time the curves are set, leads to lockout!
Error-
Diagnostic
Meaning for the LMV36... system
code
code
167
8
Manual locking by the AZL2...
Timeout / communication breakdown
Basic documentation LMV36...
23 Operating the AZL2... unit
CC1P7544en
25.09.2013