Error
Diagnostic code
code
113
#
115
#
116
0
117
0
120
0
121
#
122
#
123
#
124
#
125
#
126
#
127
#
128
0
129
#
130
#
131
#
132
#
133
#
134
#
135
#
136
1
137
#
157 (-99)
239 (-17)
240 (-16)
Building Technologies Division
Infrastructure & Citiies Sector
Meaning for the LMV36... system
Internal error mains voltage supervision
Internal error system counter
Designed life time exceeded (250´000 startups)
Life time exceeded
Operation no longer allowed
Interrupt limitation fuel meter input
Internal error EEPROM access
Internal error EEPROM access
Internal error EEPROM access
Internal error EEPROM access
Internal error EEPROM read access
Internal error EEPROM write access
Internal error EEPROM access
Internal error EEPROM access - synchronization during
initialization
Internal error EEPROM access – command
synchronization
Internal error EEPROM access - timeout
Internal error EEPROM access - page on abort
Internal error EEPROM register initialization
Internal error EEPROM access – Request synchronization
Internal error EEPROM access – Request synchronization
Internal error EEPROM access – Request synchronization
Restore started
for further diagnostic codes for error code 136, refer to
error code 137
Internal error – backup / restore
Restore – ok, but backup < data set of current system
Backup – storage of backup in AZL2... faulty
Restore – no backup in AZL2...
Basic documentation LMV36...
30 Error code list
Remedy
Make a reset; if error occurs repeatedly, replace the unit
Warning threshold has been reached. The unit should be replaced
Switch-off threshold has been reached
Too many disturbance pulses at the fuel meters input
 Improve EMC
Make a reset, repeat last parameterization / check. Restore the parameter set, if error occurs
repeatedly, replace the unit
Make a reset, repeat last parameterization / check. Restore the parameter set, if error occurs
repeatedly, replace the unit
Make a reset, repeat last parameterization / check. Restore the parameter set, if error occurs
repeatedly, replace the unit
Make a reset, repeat last parameterization / check. Restore the parameter set, if error occurs
repeatedly, replace the unit
Make a reset, repeat last parameterization / check. If error occurs repeatedly, replace the unit
Make a reset, repeat last parameterization / check. If error occurs repeatedly, replace the unit
Make a reset, repeat last parameterization / check. Restore the parameter set, if error occurs
repeatedly, replace the unit
Make a reset; if error occurs repeatedly, replace the unit
Make a reset, repeat last parameterization / check. If error occurs repeatedly, replace the unit
Make a reset, repeat last parameterization / check. If error occurs repeatedly, replace the unit
Make a reset, repeat last parameterization / check. If error occurs repeatedly, replace the unit
Make a reset; if error occurs repeatedly, replace the unit
Make a reset, repeat last parameterization / check. If error occurs repeatedly, replace the unit
Make a reset, repeat last parameterization / check. If error occurs repeatedly, replace the unit
Make a reset, repeat last parameterization / check. If error occurs repeatedly, replace the unit
Restore of a backup has been started (no error)
New devices require resetting following restore!
For measures, refer to error code 137
Restore successful, but backup data record is smaller than in the current system
Reset and repeat backup
No backup stored in AZL2...
241/248