Siemens LMV36.520A1 Basic Documentation page 85

Basic unit with integrated fuel-air ratio control for forced draft burners
Table of Contents

Advertisement

Dual fuel burner gas / light oil
with gas pilot ignition with 2
fuel valves
(Operating mode 3, 9, 16, 21)
(Operating mode 13)
Fuel valve control program
Figure 61: Light oil with gas pilot ignition – fuel valve control - program
Building Technologies Division
Infrastructure & Citiies Sector
GP2
Program
P
min
Gas
LOgp-2V
Program
V2-Oil
SV-Oil
V1-Oil
Light oil
Figure 60: Dual fuel burner gas / light oil with gas pilot ignition, with 2 fuel valves
Light oil (with gas pilot ignition)
Basic documentation LMV36...
7 Basic unit
V1-Gas
V2-Gas
P
PV-Gas
Legend for fuel trains:
1)
LO
No
LK
P LT Valve proving
Bild 313e/0114
Pmax Pressure switch-max
Pmin Pressure switch-min
PV
SA
SV
TSA... Safety time
V
Z
P
SA
max
For the valve proving function,
the pressure switch-min (Pmin)
is located between the fuel valve
(V1 / V2)
Light oil
Normally Open
Air damper
Pilot valve
Actuator
Safety valve (outdoors)
Fuel valve
Ignition
85/248