11.4 Multistage operation

This operating mode is only available when firing on oil. There is a choice of 2-stage and
3-stage operation. Hence, the burner's output can be modulated via 2 or 3 stages.
Modulation is accomplished by adjustment of the air actuator or the VSD and by
switching the fuel valves for adjusting the amount of fuel.

11.4.1 Definition of curves

Fuel-air ratio control is defined via the 2 or 3 static output points. To switch the valves on
and off, switch-on and switch-off points must be defined.
The following assignments apply:
Curve-
Meaning
point
P0
Point of ignition (not approached in the operating position)
P1
Stage 1
P2on
Switch-on point stage 2. When the angle exceeds this point, the
fuel valve for the second stage is switched on
P2_d
Presetting of point P2 with no approach
P2
Stage 2
P2of
Switch-off point stage 2. When the angle falls below this point, the
fuel valve for the second stage is switched off
P3on
Switch-on point stage 3. When the angle exceeds this point, the
fuel valve for the third stage is switched on
P3_d
Presetting of point P3 with no approach
P3
Stage 3
P3of
Switch-off point stage 3. When the angle falls below this point, the
fuel valve for the third stage is switched off
The actuator positions can be set with a resolution of 0.1°, the speeds with a resolution
of 0.1%.

11.4.2 Traveling speed

The defined ramp speeds are used.
The speed of the VSD can be adjusted separately for speed increase or decrease.
No.
Parameter
522
Ramp up
523
Ramp down
The setting also acts outside the operating position.
The running speed of the actuators is fixed at 5 seconds for a positioning angle of 90°
for SQM33.4, SQM33.5, and SQN1.
The speed is 10 seconds for a positioning angle of 90° for SQM33.6.
The SQM33.7 requires 17 seconds for a positioning angle of 90°.
Basic documentation LMV36...
11 Electronic fuel-air ratio control
Valve
V1
V1
V1
V1
V2
V2
V2
V2
V3
V3