Par.
Parameter
no.
LMV36...
163
Operating hours when unit is live
164
Number of startups resettable
165
Number of startups
166
Total number of startups
167
Fuel volume resettable [m³, l, ft³, gal]
172
Fuel 1: Operation hours resettable
174
Fuel 1: Number of startups resettable
175
Fuel 1: Number of startups
177
Fuel 1: Fuel volume resettable (m³, l, ft³, gal)
186
Software drop out delay of flame signal (100 ms)
Index = = QRB... (0 = inactive, >1)
Index 1 = ION / QRA... (0 = inactive, >3 - only 200 ms-steps)
187
Fuel 1: Software drop out delay of flame signal (100 ms)
Index = = QRB... (0 = inactive, >1)
Index 1 = ION / QRA... (0 = inactive, >3 - only 200 ms-steps)
190
Postpurging in lockout position
0 = deactivate (no-load position)
1 = active (postpurge position)
When active, the Alarm in the event of start prevention function is only
possible to a limited extent!
194
Repetition limit no flame at the end of safety time (TSA)
1 = no repetition
2...4 = 1...3 repetitions
196
Repetition limit air pressure failure
1 = no repetition
2 = 1 repetition
200
Basic unit
201
Burner operating mode (fuel train, modulating / multistage, actuators,
etc.)
-- = undefined (delete curves)
1 = G mod
2 = Gp1 mod
Building Technologies Division
Infrastructure & Citiies Sector
Number of
Type
Edit
elements
1
Std_s32
Read only
1
Std_s32
Reset
1
Std_s32
Read only
1
Std_s32
Read only
1
Std_s32
Reset
1
Std_s32
Reset
1
Std_s32
Reset
1
Std_s32
Read only
1
Std_s32
Reset
2
Std_u8
Edit
2
Std_u8
Edit
1
Selection
Edit
3
Std_u8
Edit
1
Std_u8
Edit
1
Selection
Edit / clear
Basic documentation LMV36...
29 Parameter list LMV36...
Value range
Resolution
Min
Max
0 h
9999999 h
1 h
0
9999999
1
0
9999999
1
0
9999999
1
0
99999999
1
0 h
9999999 h
1 h
0
9999999
1
0
9999999
1
0
99999999
1
0
20
1
0
20
1
0
1
1
1
2
1
1
16
1
1
27
1
Default
Password level
setting
0 h
Info / Service
0
Info / Service
0
Info / Service
0
Info / Service
0
Info / Service
0 h
Info / Service
0
Info / Service
0
Info / Service
0
Info / Service
0; 0
OEM
0; 0
OEM
0
SO
0
OEM
3
OEM
undefined
SO
217/248
CC1P7544en
25.09.2013