15.2 Fuel throughput
With the fuel meter connected, the system calculates continuously the current fuel
throughput. The time required for calculating the fuel throughput varies and lies between
1 and 10 seconds. If the meter delivers no pulses for more than 10 seconds, the display
shows 0 fuel throughput. This means that when fuel throughput is at its minimum, the
sensor should have a pulse frequency of at least 0.1 Hz. The display is smoothed to
improve the settling process. With fuel throughput at its maximum, the maximum
frequency is 300 Hz.
15.2.1 Configuration
Calculation of fuel throughput is configured based on the pulse valency of the connected
fuel meter.
No.
Parameter
128
Fuel meter: Pulse valency (pulses/volume unit)
129
Fuel meter 1: Pulse valency (pulses/volume unit)
When the pulse valency is set to 0.00, the display shows 0 throughput.
15.2.2 Reading out the fuel throughput
The current fuel throughput can be read out via the following parameter on the service
menu:
No.
Parameter
960
Fuel throughput in volume unit /h (m³/h, l/h, ft³/h, gal/h)
Display of fuel throughput is possible up to 6553 volume units/h.
Note
Display of fuel throughput up to a value of 99.9 on the service menu is made with one
decimal place, from 100 with no decimal place.
Basic documentation LMV36...