Par.
Parameter
no.
LMV36...
3 = valve proving on startup and shutdown
342
Fuel 1 gas: Valve proving evacuation time
343
Fuel 1 gas: Valve proving time test atmospheric pressure
344
Fuel 1 gas: Valve proving filling time
345
Fuel 1 gas: Valve proving time test gas pressure
346
Fuel 1 gas: Waiting time gas shortage
348
Fuel 1 gas: Postpurge time (t3) (abortion if load controller ON)
Fuel 1 oil: Active detector of flame evaluation
361
0 = QRB
1 = ION / QRA
Fuel 1 oil: Prepurging
362
0 = inactive
1 = active
365
Fuel 1 oil: Prepurge time
366
Fuel 1 oil: Preignition time
367
Fuel 1 oil: Safety time 1 (TSA1)
Fuel 1 oil: Time to respond to pressure faults within safety time 1
369
(TSA1) and safety time 2 (TSA2)
370
Fuel 1 oil: Interval 1
371
Fuel 1 oil: Safety time 2 (TSA2)
372
Fuel 1 oil: Interval 2
373
Fuel 1 oil: Afterburn time
374
Fuel 1 oil: Postpurge time (no extraneous light test)
Fuel 1 oil: Pressure switch-min input
0 = inactive
376
1 = active from phase 38
2 = active from safety time (TSA)
Fuel 1 oil: Pressure switch-max / POC input
0 = inactive
377
1 = pressure switch-max
2 = POC
Fuel 1 oil: Forced intermittent operation
379
0 = inactive
1 = active
224/248
Building Technologies Division
Infrastructure & Citiies Sector
Number of
Type
Edit
elements
1
Time
Edit
1
Time
Edit
1
Time
Edit
1
Time
Edit
1
Time
Edit
1
Time
Edit
1
Selection
Edit
1
Selection
Edit
1
Time
Edit
1
Time
Edit
1
Time
Edit
1
Time
Edit
1
Time
Edit
1
Time
Edit
1
Time
Edit
1
Time
Edit
1
Time
Edit
1
Selection
Edit
1
Selection
Edit
1
Selection
Edit
Basic documentation LMV36...
29 Parameter list LMV36...
Value range
Resolution
Min
Max
0.2 s
10 s
0.2 s
0.2 s
60 s
0.2 s
0.2 s
10 s
0.2 s
0.2 s
60 s
0.2 s
0.2 s
60 s
0.2 s
1 s
108 min
0.2 s
0
1
1
0
1
1
5 s
60 min
0.2 s
0.6 s
60 min
0.2 s
1 s
15 s
0.2 s
0.4 s
14.6 s
0.2 s
0.4 s
60 min
0.2 s
1 s
15 s
0.2 s
0.4 s
60 min
0.2 s
0.2 s
60 s
0.2 s
0.2 s
108 min
0.2 s
1
2
1
1
2
1
0
1
1
Default
Password level
setting
3 s
OEM
10 s
OEM
3 s
OEM
10 s
OEM
10 s
OEM
1 s
SO
1
SO
1
OEM
30 s
SO
2 s
SO
5 s
OEM
1.8 s
OEM
2 s
SO
10 s
OEM
2 s
SO
8 s
SO
15 s
SO
1
SO
1
SO
1
SO
CC1P7544en