11.3 Modulating operation

In modulating mode, it is possible to operate 2 actuators and 1 VSD. The burner's
output can be regulated between 20.0% (low-fire) and 100.0% (high-fire) in increments
of 0.1%. Since the actuators are never allowed to operate simultaneously, the output is
increased in small steps of 1%. In the case of an operating ramp of 20% after 100% in
32 seconds, this represents 1 step in 400 ms. Within such an output step, the air
actuator is operated in the first 200 ms, and the VSD and fuel actuator in the second
200 ms.

11.3.1 Definition of curves

The fuel-air ratio curves are defined by 10 curvepoints that are firmly distributed across
the output range. The following assignment applies:
Curvepoint
Output
P0
10%
P1
20%
P2
30%
P3
40%
P4
50%
P5
60%
P6
70%
P7
80%
P8
90%
P9
100%
The actuator positions can be set with a resolution of 0.1°.
Between the curvepoints, the positions are interpolated in a linear manner.
100
90
80
70
60
50
40
30
20
10
0
Figure 74: Definition of curves
No.
Parameter
401
Ratio control curves fuel actuator (curve setting only)
402
Ratio control curves air actuator (curve setting only)
403
Ratio control curves VSD (curve setting only)
404
Fuel 1: Ratio control curves fuel actuator (curve setting only)
405
Fuel 1: Ratio control curves air actuator (curve setting only)
406
Fuel 1: Ratio control curves VSD (curve setting only)
Basic documentation LMV36...
11 Electronic fuel-air ratio control
Meaning
Point of ignition, not approached in the operating position
Low-fire
High-fire
Fuel
Air
VSD
111/248
CC1P7544en
25.09.2013