Notes on mounting
14/248
Building Technologies Division
Infrastructure & Citiies Sector
1.2

Mounting notes

Ensure that the relevant national safety regulations and regulations relating to
standards are complied with
In geographical areas where DIN regulations apply, the requirements of VDE must
be satisfied, especially DIN / VDE 0100, 0550 and DIN / VDE 0722
1.2.1

LMV36...

The LMV36... basic unit must be secured with fixing screws M4 (UNC32) or M5
(UNC24), observing a maximum tightening torque of 1.8 Nm and using all 4 fixing
points. Additional mounting surfaces on the housing are provided to improve
mechanical stability. These must completely rest on the mounting surface to which
the unit is secured. The flatness of that mounting surface must be within a tolerance
band of 0.3 mm
Touch protection of the external fuel selector must be ensured by fitting the selector
as a separate component (e.g. in a control panel door or under the burner hood)
(103.5)
M5 x 4
103.5
Figure 1: LMV36... note on mounting
Basic documentation LMV36...
1 Safety notes
Outer contour of housing
Additional mounting
surfaces
10
217
0,3
CC1P7544en
25.09.2013