Makeup Of Error History - Siemens LMV36.520A1 Basic Documentation

Basic unit with integrated fuel-air ratio control for forced draft burners
Table of Contents

Advertisement

Deleting the error history
Building Technologies Division
Infrastructure & Citiies Sector

20.2 Makeup of error history

Parameter
Index
Description
701
Current error state, can also be error-free
Code (200 = error-free)  refer to Error code list
.01
Diagnostic code  refer to Error code list
.02
Error class  error classes
.03
Phase: Phase in which error occurred  sequence diagrams
.04
.05
Startup counter: (parameter 166) at which the error occurred
.06
Output: Burner output at which the error occurred
.07
Fuel in which error occurred
702
.01..07
Latest error in the history
.
.
.
725
.01..07
Oldest error in the history
Both the service menu and the parameter setting menu show the error history.
The display on the service menu can be deleted in a way that the only errors shown are
those that occurred after the deletion.
The error history on the parameter setting menu cannot be deleted.
For the deletion, parameter 130 must be set to 1 and then to 2 within 6 seconds.
When the parameter returns to 0, the deletion process is completed.
No.
Parameter
Delete display of error history
To delete the display: Set parameter to 1, then to 2
130
Return value 0: Job successfully completed
Return value -1: Timeout of 1_2 sequence
Basic documentation LMV36...
20 Error history
153/248
CC1P7544en